Using the 5-valve manifold
In normal operation the “isolate” valves are open while the "equalize" and "vent" valves are closed. This provides a differential pressure reading to the pressure gauge or transmitter.
To zero the instrument, first close both “vent” valves and the downstream "isolate" valve. Then open the "equalize" valve and adjust the zero setting on the instrument.
To remove the instrument, first close both "isolate" valves, then open the "equalize" valves to relieve pressure between the manifold and the instrumet.

Note: The body & trim parts on all 316/316L Valves & Manifolds comply to NACE MR-01-75 & NORSOK M-650 as standard.
Remote Mount 5-Valves Manifold Model-HM8532
Remote Mount 5-Valves Manifold Model-HM8532-2
Unit of Measure
Items Remote Mount 5-Valves Manifold Model-HM8532
HM853211F8YL
Remote Mount 5-Valves Manifolds, Model-HM8532
Remote Mount 5-Valves Manifold Model-HM8532
HM853211F8HC
Remote Mount 5-Valves Manifolds, Model-HM8532
Remote Mount 5-Valves Manifold Model-HM8532
HM853211F8M
Remote Mount 5-Valves Manifolds, Model-HM8532
Remote Mount 5-Valves Manifold Model-HM8532
HM853211F8D50
Remote Mount 5-Valves Manifolds, Model-HM8532
Remote Mount 5-Valves Manifold Model-HM8532
HM853211F8TI
Remote Mount 5-Valves Manifolds, Model-HM8532
Tip N/A Hard
Packing N/A PTFE
Inlet Connection N/A Female
Inlet Size N/A 1/2" NPT
Alloy N/A 316/316L N/A HASTELLOY® C276 N/A MONEL® N/A Super Duplex N/A Titanium
Weight N/A 5.95 lb2.7 kg
Maximum pressure at 212 ºF (100 ºC) N/A 6000 psi413 bar
Maximum pressure at 392 ºF (200 ºC) N/A 4000 psi275 bar
Maximum pressure at 842 ºF (450 ºC) N/A